Intermediate Guide Spacing/Series 1500 Laminated Bellows Expansion Joints
Nominal Size NPS
|
150 psig Design
|
300 psig Design System
|
System Pressure (psig) |
Pressure (psig)
|
50
|
100
|
150
|
50 |
100
|
150
|
200
|
300
|
2
|
26
|
20
|
17
|
23 |
18
|
16
|
14
|
12
|
2 1/2
|
34
|
26
|
22
|
30 |
24
|
21
|
18
|
15
|
3
|
40
|
30
|
25
|
35 |
28
|
24
|
21
|
18
|
4
|
45
|
34
|
29
|
38
|
31
|
27
|
24
|
20
|
5
|
54
|
41
|
34
|
47
|
37
|
32
|
29
|
24
|
6
|
60
|
46
|
39
|
57
|
45
|
38
|
33
|
28
|
8
|
79
|
59
|
49
|
72
|
56
|
47
|
41
|
34
|
10
|
97
|
71
|
59
|
89
|
68
|
57
|
50
|
42
|
12
|
107
|
79
|
66
|
97
|
75
|
63
|
56
|
46
|
14
|
113
|
83
|
68
|
103
|
78
|
66
|
58
|
48
|
Note:
(1) The values listed are the center to center distance measured in feet. (2) Pipe guide spacing is a function of the expansion joint spring rate and effective area. The tabulated values are for Series 1500
laminated expansion joints at the design pressure listed. (3) The pressures listed are design values. Guide spacing has been calculated for the test pressure (1.5 X design).
|
|
|
|
|
|
|
Copyright © Hyspan Precision Products, Inc. 2005. All rights reserved.
Hyspan ® is a registered trademark.
|
|
|